MVHR unit guide

Vent-Axia Sentinel Kinetic Plus B: specifications, filters & guide

MVHRVent-Axia

The Vent-Axia Sentinel Kinetic Plus B is a wall-mounted MVHR unit with a summer bypass and integral humidity sensor, rated SEC class A+.

  • Summer bypass
  • Evening and night-time purge
  • Integral humidity sensor
  • Hinged filter access
  • Acoustic enclosure and top box options

Buy replacement filters for Sentinel Kinetic Plus B

Vent-Axia Sentinel Kinetic Plus B MVHR unit
Image: Vent-Axia

About the Vent-Axia Sentinel Kinetic Plus B

The Sentinel Kinetic Plus B is a wall-mounted mechanical ventilation with heat recovery (MVHR) unit made by Vent-Axia. It runs continuously, drawing stale, moist air from bathrooms, toilets and kitchens and passing it through a heat exchanger that transfers heat to the fresh air supplied to bedrooms and living areas. It is intended for houses and similar dwellings under the 2010 edition of Approved Document F. The ErP product fiche gives a thermal efficiency of 90% and an energy class of SEC A+.

The Plus B has a summer bypass, a damper that sends outdoor air around the heat exchanger when the house is warmer than the indoor temperature set on the controller and the air outside is cooler, and an integral humidity sensor that raises fan speed as relative humidity rises. It is made as a right-hand unit (443028) and a left-hand unit (443028L). The casing is 630 mm high, 775 mm wide and 524 mm deep including the protrusion of the filter flap hinge, weighs 24 kg and has 150 mm duct spigots, with 180 mm and 200 mm options.

Ducting can leave the unit vertically, horizontally or both. Fan speeds are set at commissioning, with factory defaults of 20% (low), 30% (normal), 50% (boost) and 100% (purge) of maximum flow. Boost can come from the front button, a wireless switch, a light switch, a sensor or a 0-10 V input, and the integrated digital controller offers BMS connectivity, volt-free inputs and an adjustable delay-on timer. An acoustic enclosure for reduced breakout noise and an acoustic top box for reduced in-duct noise are available as options. Once commissioned, the unit should need no day-to-day intervention.

Two removable filters sit behind hinged flap panels on the casing and protect the heat recovery cell. They are ISO 45% Coarse (G3) as standard, 185 x 510 mm, and an ISO ePM10 50% (M5) grade is the optional finer alternative. The control unit shows a Check filters reminder at the interval set during commissioning, because filters that become too dirty restrict airflow or let dirt pass through to the heat exchanger. Part numbers, the filter change procedure, maintenance intervals and fault codes are set out below.

Key specs

Max. flow rate (ErP product fiche)
432.00 m³/h
Max. airflow at 100 Pa
117 l/s (421.2 m³/h)
Thermal efficiency (ErP product fiche)
90.00%
Specific power input, SPI
0.20 W/(m³/h)
Default airflow settings
Low 20%, Normal 30%, Boost 50%, Purge 100% of maximum flow
Ambient temperature limits for installation
Not above 40 °C and not below -20 °C
Operating humidity
0% to 95% RH
Storage temperature
-20 °C to +45 °C
Height (excluding spigots)
630 mm
Width (excluding spigots)
775 mm
Depth
524 mm including filter flap hinge protrusion
Weight
24 kg
Maintenance access area
540 mm x 780 mm
Supply
220-240 V AC, single phase, 50 Hz
Max. power input at max. flow rate (ErP product fiche)
173.00 W
Supply fuse
3 A, located in the fused spur
Product fuse
2 A, on the main PCB
IP rating
IP22
Spigot diameter
150 mm, with 180 mm and 200 mm options
Condensate pipe diameter
22 mm
Standard filters
2 x ISO 45% Coarse (G3), part no. 403702 (pack of 2)
Optional finer filter
ISO ePM10 50% Pollen (M5), part no. 444201 (single)
Filter size
185 x 510 mm
Control unit
LCD display with four buttons
Summer bypass and integral humidity sensor
Fitted
Sound power level LWA (ErP product fiche)
52.23 dB
Sound level at 3 m, normal / boost
24 dB(A) / 34 dB(A)
Energy class
SEC class A+
Regulations and listings
Building Regulations ADF and ADL compliant; recognised in SAP PCDB

Replacement filters for the Vent-Axia Sentinel Kinetic Plus B

How to change the filters

  1. Wait for the Check filters message

    The display shows Check filters at the interval set at commissioning. The filters are reached through the flap panels on the casing. Do not remove the unit's covers: mains voltage is present inside, and the unit must be switched off at the mains before any cover is removed.

  2. Open the filter flaps

    Open the filter flaps and take out both filters.

  3. Clean or fit new filters

    For a routine check, clean the filters gently by tapping them or by carefully using a vacuum cleaner. At a scheduled change, fit two replacement filters of 185 x 510 mm.

  4. Close the filter flaps

    Close both filter flaps.

  5. Reset the reminder

    Press and hold the up and down buttons on the control unit together for 5 seconds to clear the automatic message.

  6. Record the next change date

    Note the date of the next required filter change on the filter check record provided with the unit.

Manuals & downloads

User InstructionsPDF
Installation of the unit in the Opposite OrientationPDF
Installation & CommissioningPDF
Installer & Homeowner GuidePDF
Sentinel Kinetic Plus DatasheetPDF
Revit FileRFA
Environmental Product DeclarationPDF

Vent-Axia and all other manufacturer and product names, model numbers and part numbers on this page are the property of their respective owners and are used for identification only. MVHR.shop is an independent supplier of compatible filters. We are not affiliated with, endorsed by, sponsored by or approved by Vent-Axia or any other manufacturer named on this page.

This page is our own summary, written from documents published by the manufacturer (such as installation, user and product literature). We do not own the underlying information: all rights in the original documents, specifications, drawings and data remain with the manufacturer, and nothing here is intended to replace them.

The information is provided in good faith for general guidance only. Manufacturers revise their products and documents, specifications can differ between versions and production batches, and errors or omissions may exist, so we cannot guarantee that it is accurate, complete or up to date. Always check the manufacturer's current documentation and the rating label on your own unit before relying on any figure or part number. Nothing on this page is installation, electrical, commissioning or safety advice; work on ventilation equipment must be carried out by a competent person in line with the manufacturer's instructions and current regulations. To the fullest extent permitted by law we accept no liability for loss arising from reliance on this page. Nothing in this notice limits any liability that cannot be limited by law.

Links to other websites, including manufacturers' sites and documents, are provided for convenience only. We do not control, endorse or accept responsibility for their content, availability or privacy practices, and they may change or be removed without notice.

If you believe something on this page is wrong, or you are a rights holder with a concern, please contact us and we will review it promptly.

Specifications

Performance

Max. flow rate (ErP product fiche)
432.00 m³/h
Max. airflow at 100 Pa
117 l/s (421.2 m³/h)
Thermal efficiency (ErP product fiche)
90.00%
Specific power input, SPI
0.20 W/(m³/h)
Default airflow settings
Low 20%, Normal 30%, Boost 50%, Purge 100% of maximum flow
Ambient temperature limits for installation
Not above 40 °C and not below -20 °C
Operating humidity
0% to 95% RH
Storage temperature
-20 °C to +45 °C

Dimensions & weight

Height (excluding spigots)
630 mm
Width (excluding spigots)
775 mm
Depth
524 mm including filter flap hinge protrusion
Weight
24 kg
Maintenance access area
540 mm x 780 mm

Electrical

Supply
220-240 V AC, single phase, 50 Hz
Max. power input at max. flow rate (ErP product fiche)
173.00 W
Supply fuse
3 A, located in the fused spur
Product fuse
2 A, on the main PCB
IP rating
IP22

Connections & ducting

Spigot diameter
150 mm, with 180 mm and 200 mm options
Condensate pipe diameter
22 mm

Filters

Standard filters
2 x ISO 45% Coarse (G3), part no. 403702 (pack of 2)
Optional finer filter
ISO ePM10 50% Pollen (M5), part no. 444201 (single)
Filter size
185 x 510 mm

Controls & features

Control unit
LCD display with four buttons
Summer bypass and integral humidity sensor
Fitted

Acoustics

Sound power level LWA (ErP product fiche)
52.23 dB
Sound level at 3 m, normal / boost
24 dB(A) / 34 dB(A)

Approvals & compliance

Energy class
SEC class A+
Regulations and listings
Building Regulations ADF and ADL compliant; recognised in SAP PCDB

At a glance

Unit type
MVHR
Manufacturer
Vent-Axia
Product range
Lo-Carbon Sentinel Kinetic MVHR range
Versions
Plus B: summer bypass and integral humidity sensor
Handing
Right-hand (443028) and left-hand (443028L)
Mounting
Wall-mounted, upright; ducting vertical, horizontal or both
IP rating
IP22
Energy class
SEC class A+
Manufacturer's guarantee
2 years from date of purchase, for products installed and used in the UK
  • 432 m³/hMaximum flow rate (ErP product fiche)
  • 90%Thermal efficiency (ErP product fiche)
  • 173 WMaximum power input at maximum flow
  • 52.23 dBSound power level LWA
  • G3, 185 x 510 mmStandard filters, 2 fitted (ISO 45% Coarse)
  • 150 mmDuct spigot diameter

Vent-Axia Sentinel Kinetic Plus B features

Summer bypass

When the house is warmer than the set indoor temperature (16-40 °C, default 25 °C) and the outside air is cooler, a damper lets outdoor air skip the heat exchanger. It only works while the outdoor temperature is above 14 °C (adjustable), and it contributes to cooling rather than replacing it.

Evening and night-time purge

The bypass models can run at boost speed through the evening, stopping after at most 5 hours, or through the night, to flush warm air from the house while outdoor conditions allow.

Integral humidity sensor

Fan speed rises in step with relative humidity, and the sensor also reacts to small but rapid rises, so a steamy bathroom or kitchen is cleared without the whole system running at boost. A night-time setback reduces nuisance tripping as humidity creeps up with falling temperature.

Hinged filter access

The filters are reached through hinged flap panels without removing the unit's covers, so a routine check or change is a quick job.

Acoustic enclosure and top box options

An optional acoustic enclosure reduces breakout noise and an optional acoustic top box reduces in-duct noise at key frequencies.

Frost protection

With supply air between 0 °C and -20 °C the unit cuts the supply airflow and raises the extract rate to stop ice forming on the heat exchanger. At -20 °C or below the supply fan stops and the extract fan runs at a reduced rate.

Boost and purge

Pressing the front boost button once, twice or three times gives 30 minutes, 60 minutes or continuous boost, and holding it for 5 seconds starts a 2-hour purge at 100% fan speed.

Multiple control inputs

Boost can be triggered from a 240 V switched live, five pairs of switch terminals, a 0-10 V proportional input, a wireless switch or a wired remote controller. A building management system can also command the fans off.

Filter reminder

The display shows Check filters at the interval set at commissioning, and the reminder is cleared from the control buttons once the filters have been dealt with.

Installing the Vent-Axia Sentinel Kinetic Plus B

Mount the unit on a wall, always upright, with duct connections leaving vertically, horizontally or both. Fix the supplied metal bracket to a wall that can carry the 24 kg unit, fit the stand-off feet from the accessory bag, then hang the unit by locating its two steel wall bushes on the bracket. Keep a maintenance access area of 540 mm x 780 mm clear in front of the unit, and do not use the unit to support other equipment. In an unheated space, insulate the unit and its ducting.

The condensate pipe is fixed with a worm-drive clip to a 22 mm vertical pipe and must connect to the building's foul water drainage through a U-bend trap with at least a 60 mm water seal (or a HepVo valve), falling at least 3 degrees. Insulate the pipe if it runs through a cold void.

  • Do not install the unit where the atmosphere is excessively oily or greasy, where corrosive or flammable gases, liquids or vapours may be present, where it may be sprayed with water from hoses, or where ambient temperature may exceed 40 °C or fall below -20 °C.
  • Intake air must come from outside the property, and the unit must not be connected directly to a tumble drier.
  • Open the supply and exhaust valves fully before commissioning, and allow at least 5 minutes for the unit to stabilise when changing between boost and normal speeds.
  • Installation and the electrical connection must be carried out by suitably trained and qualified persons, with a local double-pole fused spur (3 A fuse, at least 3 mm contact separation) to isolate the supply. Switch the unit off at the mains before any cover is removed.
  • Follow the manufacturer's full installation, operation and maintenance instructions for wiring diagrams and commissioning settings.