MVHR unit guide

Vent-Axia Sentinel Kinetic High Flow: specifications, filters & guide

MVHRVent-Axia

The Vent-Axia Sentinel Kinetic High Flow is a wall-mounted MVHR unit for larger homes and multiple-occupancy buildings, with a maximum flow rate of 666 m³/h.

  • Summer bypass
  • Evening and night-time purge
  • Integral humidity sensor
  • Folding quick-change filter
  • Flexible spigot positions

Buy replacement filters for Sentinel Kinetic High Flow

Vent-Axia Sentinel Kinetic High Flow MVHR unit
Image: Vent-Axia

About the Vent-Axia Sentinel Kinetic High Flow

The Sentinel Kinetic High Flow is a wall-mounted mechanical ventilation with heat recovery (MVHR) unit made by Vent-Axia and part of the Lo-Carbon Sentinel Kinetic range. It runs continuously, drawing stale, moist air from wet rooms and kitchens and passing it through a counterflow heat exchanger that transfers heat to the fresh air supplied to living areas and bedrooms. It is designed for larger homes and multiple-occupancy buildings such as care homes and student accommodation. The ErP product fiche gives a thermal efficiency of 90% and an energy class of SEC A.

The High Flow has a summer bypass, a damper that sends outdoor air around the heat exchanger when the house is warmer than the indoor temperature set on the controller and the air outside is cooler, and an integral humidity sensor that raises fan speed in proportion to relative humidity. It is made as a right-hand unit (408449) and a left-hand unit (408451), each also available with an acoustic enclosure, an acoustic top box or both. The casing is 630 mm high and 775 mm wide, weighs 38 kg and has 180 mm duct spigots, which can be repositioned to give vertical, horizontal or combined connections, with a 200 mm option.

Fan speeds are set at commissioning, with factory defaults of 20% (low), 30% (normal), 50% (boost) and 100% (purge) of maximum flow. Boost can come from the front button, a wireless switch, a light switch, a sensor or a 0-10 V input, and the integrated digital controller offers BMS connectivity, volt-free inputs and an adjustable delay-on timer. Backward-curved impellers on EC/DC motors keep energy use down. Once commissioned, the unit should need no day-to-day intervention.

Two removable filters sit behind hinged flap panels on the casing and protect the heat recovery cell. The filter folds as it is withdrawn, which suits installations in cupboards where access is limited. They are ISO 45% Coarse (G3) as standard, 185 x 510 mm, and an ISO ePM10 50% (M5) grade is the optional finer alternative. The control unit shows a Check filters reminder at the interval set during commissioning, because filters that become too dirty restrict airflow or let dirt pass through to the heat exchanger. Part numbers, the filter change procedure, maintenance intervals and fault codes are set out below.

Key specs

Max. flow rate (ErP product fiche)
666.00 m³/h
Thermal efficiency (ErP product fiche)
90.00%
Specific power input, SPI
0.42 W/(m³/h)
Reference flow rate at 50 Pa
0.12950 m³/s
Default airflow settings
Low 20%, Normal 30%, Boost 50%, Purge 100% of maximum flow
Ambient temperature limits for installation
Not above 40 °C and not below -20 °C
Operating humidity
0% to 95% RH
Storage temperature
-20 °C to +45 °C
Height (excluding spigots)
630 mm
Width (excluding spigots)
775 mm
Depth
524 mm including filter flap hinge protrusion
Weight
38 kg
Maintenance access area
540 mm x 780 mm
Supply
220-240 V AC, single phase, 50 Hz
Max. power input at max. flow rate (ErP product fiche)
360.00 W
Supply fuse
3 A, located in the fused spur
Product fuse
2 A, on the main PCB
IP rating
IP22
Spigot diameter
180 mm, with a 200 mm option
Condensate pipe diameter
22 mm
Standard filters
2 x ISO 45% Coarse (G3), part no. 403702 (pack of 2)
Optional finer filter
ISO ePM10 50% Pollen (M5), part no. 444201 (single)
Filter size
185 x 510 mm
Control unit
LCD display with four buttons
Summer bypass and integral humidity sensor
Fitted
Sound power level LWA (ErP product fiche)
61.03 dB
Sound data test standard
BS EN 13141-7:2010
Energy class
SEC class A
Regulations and listings
Recognised in SAP PCDB

Replacement filters for the Vent-Axia Sentinel Kinetic High Flow

How to change the filters

  1. Wait for the Check filters message

    The display shows Check filters at the interval set at commissioning. The filters are reached through the flap panels on the casing. Do not remove the unit's covers: mains voltage is present inside, and the unit must be switched off at the mains before any cover is removed.

  2. Open the filter flaps

    Open the filter flaps and take out both filters. The filter folds as it is withdrawn.

  3. Clean or fit new filters

    For a routine check, clean the filters gently by tapping them or by carefully using a vacuum cleaner. At a scheduled change, fit two replacement filters of 185 x 510 mm.

  4. Close the filter flaps

    Close both filter flaps.

  5. Reset the reminder

    Press and hold the up and down buttons on the control unit together for 5 seconds to clear the automatic message.

  6. Record the next change date

    Note the date of the next required filter change on the filter check record provided with the unit.

Manuals & downloads

Installation & CommissioningPDF
Installer & Homeowner GuidePDF
User InstructionsPDF
Installation of the unit in the Opposite OrientationPDF
Sentinel Kinetic High Flow DatasheetPDF
Case Study - Kingswood, SurreyPDF
Case Study - County Down, Northern IrelandPDF
3D Revit FileRFA
Verified EPDPDF

Vent-Axia and all other manufacturer and product names, model numbers and part numbers on this page are the property of their respective owners and are used for identification only. MVHR.shop is an independent supplier of compatible filters. We are not affiliated with, endorsed by, sponsored by or approved by Vent-Axia or any other manufacturer named on this page.

This page is our own summary, written from documents published by the manufacturer (such as installation, user and product literature). We do not own the underlying information: all rights in the original documents, specifications, drawings and data remain with the manufacturer, and nothing here is intended to replace them.

The information is provided in good faith for general guidance only. Manufacturers revise their products and documents, specifications can differ between versions and production batches, and errors or omissions may exist, so we cannot guarantee that it is accurate, complete or up to date. Always check the manufacturer's current documentation and the rating label on your own unit before relying on any figure or part number. Nothing on this page is installation, electrical, commissioning or safety advice; work on ventilation equipment must be carried out by a competent person in line with the manufacturer's instructions and current regulations. To the fullest extent permitted by law we accept no liability for loss arising from reliance on this page. Nothing in this notice limits any liability that cannot be limited by law.

Links to other websites, including manufacturers' sites and documents, are provided for convenience only. We do not control, endorse or accept responsibility for their content, availability or privacy practices, and they may change or be removed without notice.

If you believe something on this page is wrong, or you are a rights holder with a concern, please contact us and we will review it promptly.

Specifications

Performance

Max. flow rate (ErP product fiche)
666.00 m³/h
Thermal efficiency (ErP product fiche)
90.00%
Specific power input, SPI
0.42 W/(m³/h)
Reference flow rate at 50 Pa
0.12950 m³/s
Default airflow settings
Low 20%, Normal 30%, Boost 50%, Purge 100% of maximum flow
Ambient temperature limits for installation
Not above 40 °C and not below -20 °C
Operating humidity
0% to 95% RH
Storage temperature
-20 °C to +45 °C

Dimensions & weight

Height (excluding spigots)
630 mm
Width (excluding spigots)
775 mm
Depth
524 mm including filter flap hinge protrusion
Weight
38 kg
Maintenance access area
540 mm x 780 mm

Electrical

Supply
220-240 V AC, single phase, 50 Hz
Max. power input at max. flow rate (ErP product fiche)
360.00 W
Supply fuse
3 A, located in the fused spur
Product fuse
2 A, on the main PCB
IP rating
IP22

Connections & ducting

Spigot diameter
180 mm, with a 200 mm option
Condensate pipe diameter
22 mm

Filters

Standard filters
2 x ISO 45% Coarse (G3), part no. 403702 (pack of 2)
Optional finer filter
ISO ePM10 50% Pollen (M5), part no. 444201 (single)
Filter size
185 x 510 mm

Controls & features

Control unit
LCD display with four buttons
Summer bypass and integral humidity sensor
Fitted

Acoustics

Sound power level LWA (ErP product fiche)
61.03 dB
Sound data test standard
BS EN 13141-7:2010

Approvals & compliance

Energy class
SEC class A
Regulations and listings
Recognised in SAP PCDB

At a glance

Unit type
MVHR
Manufacturer
Vent-Axia
Product range
Lo-Carbon Sentinel Kinetic MVHR range
Versions
High Flow with summer bypass and integral humidity sensor; acoustic enclosure and top box options
Handing
Right-hand (408449) and left-hand (408451)
Mounting
Wall-mounted, upright; ducting vertical, horizontal or both
IP rating
IP22
Energy class
SEC class A
Manufacturer's guarantee
2 years from date of purchase, for products installed and used in the UK
  • 666 m³/hMaximum flow rate (ErP product fiche)
  • 90%Thermal efficiency (ErP product fiche)
  • 360 WMaximum power input at maximum flow
  • 61.03 dBSound power level LWA (ErP product fiche)
  • G3, 185 x 510 mmStandard filters, 2 fitted (ISO 45% Coarse)
  • 180 mmDuct spigot diameter, 200 mm option

Vent-Axia Sentinel Kinetic High Flow features

Summer bypass

When the house is warmer than the set indoor temperature (16-40 °C, default 25 °C) and the outside air is cooler, a damper lets outdoor air skip the heat exchanger. It only works while the outdoor temperature is above 14 °C (adjustable), and it contributes to cooling rather than replacing it.

Evening and night-time purge

The bypass models can run at boost speed through the evening, stopping after at most 5 hours, or through the night, to flush warm air from the house while outdoor conditions allow.

Integral humidity sensor

Fan speed rises in step with relative humidity, and the sensor also reacts to small but rapid rises, so even a small wet room is cleared without the whole system running at boost. A night-time setback reduces nuisance tripping as humidity creeps up with falling temperature.

Folding quick-change filter

The filter folds as it is withdrawn, so it can be removed through the hinged flaps even in a cupboard with restricted access.

Flexible spigot positions

The 180 mm or 200 mm spigots can be repositioned to give a horizontal connection or a mix of vertical and horizontal connections, which suits space-saving installations.

Acoustic enclosure and top box options

An optional acoustic enclosure reduces breakout noise and an optional acoustic top box reduces in-duct noise at key frequencies. Sound data is published for the unit alone and for the unit with the enclosure.

Frost protection

With supply air between 0 °C and -20 °C the unit cuts the supply airflow and raises the extract rate to stop ice forming on the heat exchanger. At -20 °C or below the supply fan stops and the extract fan runs at a reduced rate.

Boost and purge

Pressing the front boost button once, twice or three times gives 30 minutes, 60 minutes or continuous boost, and holding it for 5 seconds starts a 2-hour purge at 100% fan speed.

BMS connectivity and multiple control inputs

The unit offers BMS status and fault reporting, volt-free inputs and light-switch inputs. Boost can also come from five pairs of switch terminals, a 0-10 V proportional input, a wireless switch or a wired remote controller.

Installing the Vent-Axia Sentinel Kinetic High Flow

Mount the unit on a wall, always upright, with duct connections leaving vertically, horizontally or both. Fix the supplied metal bracket to a wall that can carry the 38 kg unit, fit the stand-off feet from the accessory bag, then hang the unit by locating its two steel wall bushes on the bracket. Keep a maintenance access area of 540 mm x 780 mm clear in front of the unit, and do not use the unit to support other equipment. In an unheated space, insulate the unit and its ducting.

The condensate pipe is fixed with a worm-drive clip to a 22 mm vertical pipe and must connect to the building's foul water drainage through a U-bend trap with at least a 60 mm water seal (or a HepVo valve), falling at least 3 degrees. Insulate the pipe if it runs through a cold void.

  • Do not install the unit where the atmosphere is excessively oily or greasy, where corrosive or flammable gases, liquids or vapours may be present, where it may be sprayed with water from hoses, or where ambient temperature may exceed 40 °C or fall below -20 °C.
  • Intake air must come from outside the property, and the unit must not be connected directly to a tumble drier.
  • Open the supply and exhaust valves fully before commissioning, and allow at least 5 minutes for the unit to stabilise when changing between boost and normal speeds.
  • Installation and the electrical connection must be carried out by suitably trained and qualified persons, with a local double-pole fused spur (3 A fuse, at least 3 mm contact separation) to isolate the supply. Switch the unit off at the mains before any cover is removed.
  • Follow the manufacturer's full installation, operation and maintenance instructions for wiring diagrams and commissioning settings.